Mini-Split Support Center

Troubleshooting guides and answers to common questions

1 What issue are you experiencing?

Select the category that best describes your problem.

2 Describe your heating problem

Select the option that matches your situation.

Troubleshooting: No Heat / Blowing Cold Air

  • Check the mode: Ensure the remote is set to HEAT mode (sun icon), not AUTO or COOL
  • Set temperature correctly: Set temperature higher than room temperature (at least 3-5° above)
  • Wait for defrost cycle: In cold weather, the outdoor unit may run a defrost cycle for 5-10 minutes
  • Check outdoor unit: Verify the outdoor unit fan is spinning and compressor is running
  • Touch the line set: In heat mode, the suction line (larger) should feel warm, and the liquid line (smaller) should be hot. If both are cold, system may be low on refrigerant or have a reversing valve issue
  • Verify refrigerant pressure: In heat mode, PSI should read 400-450 PSI

If outdoor unit shows E19, see Error Code 19 troubleshooting

Troubleshooting: Blower Shuts Off Immediately in Heat Mode

  • Low refrigerant: This is the most common cause. In heat mode, the indoor coil must reach a certain temperature before the blower will run
  • Check error code 13: If you see E13, the refrigerant level is likely too low to heat the coil properly
  • Touch the outdoor lines: If the suction line (larger line) feels cool or just slightly warm, and the liquid line (smaller line) is not hot, the system is likely low on charge
  • Unit may cool fine: It's common for a unit to work in cooling mode but fail in heating mode due to low refrigerant
  • Have a technician check: Locate and repair any refrigerant leak, then evacuate and recharge the system to factory specifications

Even if the unit appears charged to label specifications, additional refrigerant may be needed for proper heating operation.

Troubleshooting: Unit Cools But Won't Heat

  • Check reversing valve: The reversing valve switches between cooling and heating - it may be stuck or faulty
  • Both lines cold in heat mode? If both suction and liquid lines are cold, the system pressures are likely balanced, suggesting a failed reversing valve (stuck in cooling position or leaking internally)
  • Low refrigerant: Your unit can cool properly but fail to heat due to insufficient refrigerant
  • Verify wiring: Ensure all wire connections between indoor and outdoor units are secure
  • Check outdoor temperature: Heat pumps are less efficient below 40°F - some units have minimum operating temps
  • Listen for click: When switching to heat, you should hear a "click" from the reversing valve

This issue often requires professional diagnosis. If basic checks don't resolve it, a technician report is needed.

Heat Pump Freezing in Cold Weather (Below 40°F)

  • Normal operation: Heat pumps become less efficient as outdoor temperatures drop, especially below 40°F
  • Defrost cycle is normal: The outdoor unit will periodically run in reverse to melt accumulated ice/frost (takes 5-15 minutes)
  • During defrost: Indoor fan may blow cool air or shut off temporarily - this is normal
  • Check for low refrigerant: If unit struggles below 40°F, low refrigerant is the most common cause - unit needs more charge in cold temps
  • Ice buildup on outdoor coil? Minor frost is normal, but heavy ice coating indicates airflow restriction or low charge
  • Line set temperature check: In heat mode at 35-40°F outdoor temp, suction line (larger) should feel warm/hot and liquid line (smaller) should be very hot. If cool, refrigerant is low
  • Minimum operating temperature: Most residential heat pumps have minimum operating temps (typically 5-15°F). Check your manual
  • Consider backup heat: For consistent heating below 35°F, a backup heating source (electric or gas) is recommended

Common Issue: Units that cool fine in summer but fail to heat in winter almost always have low refrigerant. Have a technician check charge levels and repair any leaks.

Pro Tip: If your outdoor unit is completely covered in ice and won't defrost, turn unit OFF for 30-60 minutes to allow manual defrost, then restart. If ice returns quickly, call for service.

Error Code 19 E19 - Outdoor Control Board Fault

  • Power cycle the unit: Turn off at breaker for 5 minutes, then restart
  • Check for power surges: Control boards commonly fail due to electrical surges - install a surge protector
  • Check for critters: Small animals (lizards, snakes, rodents) can get inside the outdoor unit and cause damage
  • Inspect outdoor coils: Clean any debris, ice, or dirt from outdoor unit coils
  • Verify voltage: Ensure proper voltage supply to outdoor unit (230V or 115V depending on model - check nameplate)
  • Check compressor: If compressor isn't starting, the capacitor or compressor itself may be faulty

Error 19 typically indicates the outdoor control board needs replacement. If issue persists after power cycle, contact support with your model and batch number.

SURGE PROTECTOR REQUIRED: Replacement boards that fail due to power surges without a surge protector installed are NOT covered under warranty.

Troubleshooting: Compressor Not Running

  • Check power supply: Verify proper voltage at outdoor unit disconnect (230V or 115V depending on model - check nameplate)
  • Listen for sounds: Humming = possible bad capacitor. Clicking = possible relay issue
  • Check for error codes: Note any codes on indoor display (E19 is common)
  • Check LED lights: Remove outdoor unit top panel and observe LED pattern on control board
  • Inspect control board: If the board shows signs of damage (burn marks, bulging components), the entire board needs replacement
  • Verify thermostat demand: Indoor unit must be calling for heat/cool
  • Check overload protection: Compressor may have thermal overload - let it cool down 30 minutes
  • Compressor shorted? If a technician finds the compressor shorted to ground on all terminals, the compressor has failed and needs replacement

If indoor fan runs but compressor won't start, document the issue and contact support for warranty evaluation.

Troubleshooting: Cooling Issues

  • Check mode setting: Ensure unit is in COOL mode (snowflake icon)
  • Set temperature lower: Temperature must be set below current room temp
  • Clean filters: Dirty filters drastically reduce cooling capacity
  • Check outdoor unit: Ensure outdoor coils are clean and fan is running
  • Verify refrigerant: Low refrigerant causes poor cooling - check for leaks
  • Check airflow: Ensure vents aren't blocked and louvers are open

Troubleshooting: Remote Control Issues

Unit not responding to remote or settings "locked"

  • Check for beep: If you hear a beep when pressing buttons, the unit is receiving the signal - remote is working
  • Replace batteries: Weak batteries are the most common cause - replace with fresh AAA batteries
  • Check battery polarity: Ensure batteries are installed with correct +/- orientation
  • Unit locked? Some remotes have a lock function - check for a lock icon on display
  • Remote sensor blocked? Ensure nothing is blocking the sensor on the indoor unit
  • Distance test: Try operating from different distances and angles
  • Power cycle unit: Turn off at breaker for 5 minutes to reset any software glitches
  • Test with different remote: If available, try another compatible remote to isolate the issue
  • Settings won't change: If unit blows air but won't respond to temperature/mode changes, the remote may need replacement

Replacement Remotes: Universal mini-split remotes are available online, or contact support for an OEM replacement. Provide your model number when ordering.

Troubleshooting: Unit Tripping Breaker

Unit has power but won't turn on, or trips breaker when starting

  • Verify voltage supply: Unit requires 230V or 115V depending on model - have an electrician test voltage at the disconnect box and compare to nameplate
  • Check breaker size: Ensure breaker is properly sized for your unit (typically 15-20A for residential units)
  • Test L1-L2 voltage: Should read approximately 230V between L1 and L2 for 230V models, or 115V for 115V models
  • Test neutral-line voltage: For 230V models, check voltage between Neutral and each line (L1 and L2) - should read ~115V each. For 115V models, verify 115V at the supply
  • Inspect wiring connections: Look for loose, corroded, or overheating connections at both units
  • Check for short circuit: A short in wiring or components will trip breaker immediately
  • Damaged compressor: A shorted compressor will trip breaker on startup
  • Failed control board: Indoor unit electrical failure can prevent power-up
  • Extreme cold conditions: Units may struggle to start in polar vortex conditions (below -10°F)

Safety First: All electrical troubleshooting should be performed by a licensed electrician. Working with 230V or 115V power is dangerous and can cause serious injury or death.

Professional Diagnosis Required: If voltage is correct and unit still won't power on or trips breaker, document the issue with photos/video and contact support. A technician's diagnostic report may be needed for warranty evaluation.

2 Which error code is displayed?

Select your error code below.

Error Code 6 E6 - Voltage/Electrical Issue

  • Check voltage supply: Unit requires 230V or 115V depending on model - verify with multimeter against nameplate rating
  • Inspect wiring: Look for loose or damaged wire connections - connections may be loose or wired incorrectly
  • Check breaker: Ensure dedicated breaker is properly sized (230V or 115V depending on model)
  • Verify neutral/ground: Proper grounding is essential for operation
  • Check wire gauge: Ensure proper gauge wire for the distance run - refer to nameplate on outdoor unit

Electrical work should be performed by a qualified electrician. Incorrect voltage will damage the unit.

Error Code 12 E12 - Outdoor Temperature Sensor Issue

LED Pattern: Solid / Blinking / Blinking

  • Primary causes: Outdoor temperature sensor dirty, faulty, or ambient temperature too cold to operate
  • DIY Fix - Clean the sensor: Locate the small black tube on the top corner of the outdoor coil
  • Cleaning procedure: Gently wash the sensor with warm water to remove dirt, debris, or frost buildup
  • Test after cleaning: Power cycle the unit (off at breaker for 5 minutes) and restart
  • Too cold to operate? E12 can appear if outdoor temperature is below the unit's minimum operating range (typically 5-15°F for heating)
  • Check service valve caps: Missing caps can cause slow refrigerant leaks, which may trigger this error
  • Low refrigerant connection: This error can also indicate low refrigerant - check line temperatures
  • Sensor replacement: If cleaning doesn't resolve the issue, the outdoor temperature sensor may need replacement

If error persists after cleaning sensor and power cycle, check refrigerant levels. Units low on refrigerant often show E12.

Sensor Location: The outdoor temperature sensor is a small black thermistor tube located at the top corner of the outdoor coil. It's about the size of a pencil and clips onto the coil fins.

Error Code 13 E13 - Low Refrigerant / Temperature Issue

  • Low refrigerant: This error typically indicates the refrigerant level is too low to heat the indoor coil to the required temperature
  • Blower won't run in heat: The indoor blower fan won't trigger if the coil can't reach a certain temperature
  • Touch the outdoor lines: In heat mode, lines should feel warm/hot. If cool or just slightly warm, refrigerant is low
  • AC may work fine: The unit may cool properly but fail in heating mode due to insufficient charge
  • Have a tech check: Contact your local HVAC technician to refill refrigerant and check for leaks

If outdoor LEDs are all flashing with E13, the system definitely needs refrigerant service.

Error Code 15 E15 - Temperature Sensor / Low Refrigerant

  • Primary cause: Temperature sensor issue or low refrigerant charge
  • Check line temperatures: Touch the outdoor lines - if suction line (larger) is cool/warm instead of hot, refrigerant is low
  • Sensor failure: The outdoor coil temperature sensor may have failed or become disconnected
  • Verify sensor connection: Check that the outdoor coil sensor is plugged into the control board
  • Test sensor resistance: A technician can test the sensor with a multimeter (typical resistance: 5-50kΩ depending on temperature)
  • Refrigerant leak check: If sensor is OK, have technician check for refrigerant leaks and recharge system
  • Power cycle: Turn off at breaker for 5 minutes, then restart - if error returns immediately, likely sensor failure

E15 in heating mode almost always indicates low refrigerant. Have a tech check charge levels and repair any leaks.

Error Code 17 E17 - Indoor/Outdoor Communication Failure

  • Communication failure: Error 17 indicates the indoor and outdoor units cannot communicate properly
  • Symptom: Fan may blow briefly then stop, unit won't heat or cool
  • Power cycle first: Turn off at breaker for 5 minutes, then restart
  • Check communication wiring: Verify all wires between indoor and outdoor units are securely connected
  • Inspect terminals: Look for loose, corroded, or damaged wire connections at both units
  • Verify wiring order: Ensure wires are connected according to the wiring diagram (typically Ground, White, Black)
  • Outdoor control board: If wiring is correct and error persists, the outdoor control board likely needs replacement
  • Check for surge damage: Power surges are a common cause of board failure

If error persists after power cycle and wiring check, the outdoor control board will need replacement.

To request a warranty replacement, you'll need: proof of purchase, model number, batch number (starts with "K-"), and shipping address.

Error Code 18 E18 - DC Compressor Start Failure

  • Compressor won't start: The DC inverter compressor is failing to start or reach required speed
  • Check power supply: Verify proper voltage at outdoor unit (230V or 115V depending on model) - low voltage can prevent compressor start
  • Inspect control board: If the board shows signs of damage (burn marks, bulging components), the entire board needs replacement
  • Check outdoor temperature: E18 can occur if outdoor temp is outside operating range (too cold or too hot)
  • Refrigerant level: Low refrigerant can cause compressor to fail startup checks
  • Outdoor control board: The board may not be sending proper signals to the compressor - may need replacement
  • Compressor failure: If all else checks out, the compressor itself may have failed (shorted windings, seized mechanically)
  • Power cycle test: Turn off at breaker for 10 minutes to allow compressor to cool, then restart

If error persists after power cycle and voltage verification, document the issue and contact support for warranty evaluation. Include model, batch number, and a technician's diagnosis if available.

Error Code 36 E36 - Communication Failure

  • Indoor/Outdoor communication: E36 indicates a communication failure between the indoor and outdoor units
  • Check cable connections: Ensure all communication cables between units are securely connected
  • Inspect wire terminals: Look for loose, damaged, or corroded connections at both units
  • Verify wiring order: Check that wires are connected in the correct order per the wiring diagram (Ground, White, Black)
  • Check outdoor LED lights: If outdoor LEDs don't light up at all, the outdoor board may be damaged
  • Power cycle: Turn off at breaker for 5 minutes, check all connections, then restart

If LEDs on outdoor board don't light up, the control board may need replacement. Try unplugging the fan motor connector to test if the board powers up.

Error Code 39 E39 - Indoor Fan Motor Issue

  • Check for obstructions: Make sure nothing is blocking the indoor fan motor
  • Check fan motor connection: Verify the fan motor cord is securely connected to the indoor board
  • Test the fan motor: If connections are good and there's no blockage, the fan motor may have failed
  • Indoor control board: If the fan motor is functional, the indoor control board may need replacement
  • Get a tech report: A technician can verify whether the motor or board needs replacement

Other Error Codes

Common additional codes include E14, E16, E34, E74, and E77. For these codes:

  • Document the code: Note the exact error code displayed
  • Power cycle first: Turn off at breaker for 5 minutes, then restart
  • Check your manual: Error code meanings are listed in your unit's documentation
  • Get both codes: Check the indoor display AND the outdoor LED pattern
  • Multiple codes: If seeing multiple codes (e.g., 16, 19, 77, 74, 34), contact support with all codes

Multiple simultaneous error codes often indicate a more serious issue requiring professional diagnosis.

2 What installation help do you need?

Select the topic you need assistance with.

Vacuum & Refrigerant Line Setup

  • Yes, you need to vacuum: All air and moisture must be evacuated from lines before releasing refrigerant
  • 3/8" to 1/4" adapter required: Most units have 3/8" service valves, but standard vacuum hoses are 1/4" - you'll need a "3/8" Female SAE × 1/4" Male SAE adapter" available at HVAC supply stores or online
  • Use a vacuum pump: Pull vacuum to at least 500 microns (lower is better)
  • Hold vacuum test: System should hold vacuum for 15-30 minutes without rising
  • Vacuum rising quickly? Indicates a leak - check all flare connections
  • Check service valve caps: Before starting, verify all service valve caps are present and tight - missing caps cause slow refrigerant leaks
  • After vacuum: Open service valves slowly to release refrigerant into lines
  • Replace caps after vacuum: Ensure all service valve caps are reinstalled after releasing refrigerant
  • Line set shortening: There is no minimum line set length - just coil any excess

Never release refrigerant without first evacuating the lines. Moisture will damage the compressor.

Missing Adapter? Many installers don't realize they need the 3/8" to 1/4" adapter. Search online for "3/8 Female SAE 1/4 Male SAE adapter" or check your local HVAC supply store. This adapter is NOT included with the unit.

Mounting & Placement Guidelines

  • Indoor unit height: Mount 7-8 feet from floor, at least 6 inches from ceiling
  • Wall clearance: Minimum 4-6 inches from side walls for proper airflow
  • Outdoor unit: Place on level surface, 12+ inches from walls
  • Line set routing: Keep lines as short as possible, avoid kinks
  • Drainage: Indoor unit must have proper condensate drain slope

Wiring & Electrical Setup

  • Power requirement: Units require either 230V or 115V dedicated circuit depending on model - check the nameplate on the outdoor unit
  • Power cable (breaker to unit): The power cable from the breaker to the unit has 3 wires: green, white, and black
  • Communication cable (connects the 2 units): The communication cable that connects the indoor and outdoor units together has 4 wires: white, black, red, and green
  • Proper wire gauge: Check the nameplate on the outdoor unit for required wire gauge
  • Control board: Outdoor control boards come pre-programmed - no additional programming needed
  • Ground wire: Always connect ground wire for safety

All electrical work should comply with local codes. Hire a licensed electrician if unsure.

Installation Component Checklist & Missing Parts

Before starting installation, verify you have ALL these components. Missing parts are a common installation delay!

Indoor Unit Package Should Include:

  • Indoor air handler unit with mounting plate
  • Remote control with batteries
  • Indoor unit mounting hardware (screws, anchors)
  • Drain tubing for condensate
  • Owner's manual and installation instructions

Outdoor Unit Package Should Include:

  • Outdoor condenser unit
  • Outdoor mounting brackets or pad (depending on model)
  • Service port caps (often pre-installed on unit)
  • Installation manual

Typically NOT Included (Sold Separately):

  • Refrigerant line set - Must purchase separately (ensure correct size and length for your model)
  • Communication/control wire (14/4 or 16/4 stranded) between indoor/outdoor units
  • Power wire from breaker panel to outdoor unit (consult electrician for proper gauge)
  • Disconnect box for outdoor unit (required by code)
  • Wall penetration kit (wall sleeves, escutcheon plates)
  • Condensate drain pump (if needed for your installation)

Model Compatibility Check: Verify your indoor and outdoor unit model numbers match! Example: H12FB1 indoor must pair with H12E1 or H12FB2 outdoor (same tonnage/BTU rating). Mismatched units will not work together.

Missing Components? Check all packaging thoroughly - components may be in separate bags/boxes. If genuinely missing, contact support with proof of purchase, model number, and photos of what you received. We can ship missing installation components under warranty.

Leak & Refrigerant Issues

  • Indoor coil leaking water? Check condensate drain for clogs, verify unit is level
  • Outdoor unit leaking refrigerant? Look for oily residue around connections - this indicates refrigerant leak
  • Oil in the condenser base? This is a sign of refrigerant leak - the oil residue comes from the refrigerant
  • Ice forming on lines? Often indicates low refrigerant or airflow restriction
  • Check flare connections: Most leaks occur at indoor/outdoor unit flare connections. Use soapy water to identify bubbling
  • Flare won't tighten? If the flare is as tight as possible but still leaks, the flare fitting may be damaged
  • Compressor area leak? May require compressor or unit replacement under warranty

Refrigerant leaks require a technician with EPA certification to repair. Document with photos/videos and contact support for warranty claim.

Parts & Warranty Information

  • Parts warranty: Replacement parts are covered for 1 year from proof of purchase or installation date
  • Compressor warranty: The compressor is covered for up to 7 years
  • Indoor unit coil warranty: The indoor unit has a 2-year warranty on the coils when any leaks occur
  • DIY installations: Warranty starts 3 months after manufacturing date if no proof of purchase
  • Labor NOT covered: Our warranty does NOT cover labor or services provided by technicians, electricians, or HVAC professionals
  • Surge protector required: Replacement boards that fail due to power surges without surge protection are NOT covered
  • For warranty claims: You'll need proof of purchase, model number, serial number, batch number (K-XXXX), photos of issue, and for major components - a technician's diagnosis report

Single-Zone Only: Hessaire mini-splits are single-zone units. One indoor unit pairs with one outdoor unit - they are not multi-zone compatible.

How to Get Error Codes

To retrieve error codes, you need to check both the indoor and outdoor units using different methods:

Method 1: Indoor Unit Error Codes

  1. Make sure the unit has been powered on for at least 5 minutes
  2. Use the remote control and press the "Sleep" button 10 times within 10 seconds
  3. Wait to hear a "beep" between each press
  4. If an error code is present, it will be displayed on the indoor unit's display panel
  5. If two malfunctions occur, press the "Sleep" button an additional 10 times

Method 2: Outdoor Unit Error Codes (LED Display)

  1. The unit should be running for at least 5 minutes before checking
  2. Use extreme caution! Remove the top panel of the outdoor unit (secured with three screws)
  3. Remove the back cover from the control board to expose the LED display lights
  4. Observe the pattern of LEDs 1, 2, and 3: Solid On / Solid Off / Blinking
  5. Record the pattern (e.g., "flash/off/solid on")
  6. Refer to the "Error Code Table" in your user manual to interpret the pattern

Important: Always provide both the indoor error code AND the outdoor LED pattern when contacting support.

If no code appears on the indoor unit after pressing the Sleep button 10 times:

  • Check the outdoor unit's LED pattern - the error may be outdoor-only
  • No error code displayed often means low refrigerant - this is the most common cause
  • Touch the outdoor line set during heating mode: if the suction line (larger) feels cool or just slightly warm, and the liquid line (smaller) is not hot, the system is likely low on charge

Heating Problems

The most common cause is low refrigerant. A unit can cool fine but fail to heat because:

  • In heat mode, the indoor coil must reach a specific temperature before the blower runs
  • Low refrigerant prevents the coil from getting hot enough
  • Heat pumps are less efficient as temps drop below 40°F
  • Have a technician check and recharge refrigerant if needed

In heat mode, the high-side pressure should be approximately 400-450 PSI. If pressures are significantly lower, the system likely needs refrigerant.

Error Codes

E19 indicates an outdoor control board fault. Common causes:

  • Power surge damage (most common)
  • Animal intrusion in outdoor unit
  • Faulty capacitor or compressor

Try power cycling first. If issue persists, the outdoor control board likely needs replacement.

E13 typically indicates the system is low on refrigerant. The indoor coil can't reach the required temperature, so the blower won't run. Have a technician check for leaks and recharge the system.

Installation

Yes, absolutely. You must vacuum the line set to at least 500 microns before releasing refrigerant. Moisture in the lines will damage the compressor.

Hessaire mini-splits require either 230V or 115V on a dedicated circuit depending on the model. Check your unit's nameplate for specific voltage requirements. Using incorrect voltage will damage the unit and void warranty.

Warranty & Parts

  • Parts: 1 year from purchase/installation
  • Compressor: Up to 7 years
  • Indoor unit coils: 2 years for any leaks
  • NOT covered: Labor, technician services, surge damage without surge protector

Keep your proof of purchase - warranty claims require it.

Yes. Control board failures caused by power surges are NOT covered under warranty unless a surge protector was installed. We strongly recommend installing a surge protector for all mini-split installations.

Still Need Help?

Our support team is ready to assist you with any questions.

Contact Support